← All activities

The 4 to 20 mA loop

Step 1
tank level 50 % level transmitter two wire, loop powered 12.0 mA it regulates the current in the loop two conductors, 300 m 24 V supply + Controller analog input 250 Ω 3.00 V ADC 16 bit 9830 counts 350 GPM y = (700/13107)x − 175 loop current, mA tank level, percent